亚洲色吧-特黄三级又爽又粗又大-欧美日韩黄-好吊日av-永久免费看mv网站入口亚洲-寂寞d奶大胸少妇-人人看超碰-淫片网站-天天做天天摸-国产色综合网-久久午夜场

Welcome to Da Bai Electronic Technology (Shanghai) Co., Ltd.
Position
Home > News > Industry news
Huichuan frequency converter MD520 series alarm E005.1 bus overvoltage solution
2025/5/5 21:36:53

Huichuan frequency converter MD520 series alarm E005.1 bus overvoltage solution
Reason for malfunction:
A5-09 Set the overvoltage point in V units and do not make significant modifications. More fault causes can be self diagnosed by connecting the frequency converter to the WiFi module through a mobile app, which can assist users in quickly locating the cause of the fault.
1. Output grounding
2. Encoder interference/disconnection
3. Motor deceleration power generation
4. The synchronous machine reports a fault and shuts down after running fast
5. Wrong selection of braking resistor
6. Braking resistor phase loss
7. Overshoot power generation when vector control speed reaches
8. VF oscillation
9. Inverter model setting error
Solution:
1. 1. Check if there is a short circuit at the output terminal. 2. Check if there is a short circuit in the power cable. 3. Check if the motor resistance is symmetrical.
2. 1. Confirm if the encoder wiring is secure. 2. Confirm if the encoder cable is grounded at the frequency converter end. 3. The motor casing is grounded. 4. Try replacing the encoder and encoder cable.
3. If there is no active load (gravity load, tension load, etc.), overvoltage suppression can be activated. If conditions permit, a braking resistor can be connected. VF is F3-19, and vector control is enabled by the second bit (bit1) VdcMax of AB-25 (first motor parameter).
4. Please set F9-67/68 for the synchronous machine. Setting a shorter overspeed protection time can effectively prevent the back electromotive force from exceeding the overvoltage point of the frequency converter after the runaway.
5. The power of the braking module shall not be less than the power of the inverter. For continuous load, it can be selected according to 0.8 times the motor power, and for short-term overload, it can reach 1.5 times the motor power.
6. Check if the braking resistor is properly connected.
7. The speed loop overshoot is severe, and arc RFG and acceleration feedforward can be configured to improve the speed loop tracking performance.
8. Turn on the oscillation suppression function and optimize the VF oscillation suppression coefficient.
9. Set the correct frequency converter model
MD520 series manual free download link

Scan QR codeClose
主站蜘蛛池模板: 岗巴县| 桐柏县| 邓州市| 绥芬河市| 铁岭市| 彰化县| 克拉玛依市| 舒城县| 沙雅县| 万源市| 金山区| 浮山县| 桂平市| 辰溪县| 武定县| 加查县| 苗栗市| 桦南县| 衡东县| 哈尔滨市| 巴林右旗| 大宁县| 惠安县| 广安市| 乐昌市| 汶川县| 托克逊县| 乌拉特后旗| 岑溪市| 浠水县| 会昌县| 南岸区| 古交市| 平利县| 彭州市| 阿拉善右旗| 清徐县| 黄冈市| 剑河县| 洪湖市| 珲春市|